D11 Series High-Voltage Insulation Tester

|
D1115
|
D1110
|
D1105
|
||
|
Output voltage
|
40 V to 15000 V
|
40 V to 12000 V
|
40 V to 5000 V
|
|
|
Test voltage accuracy
|
+4%, -0%, ±10 V nominal test voltage at 1 GΩ load (0-30°C)
|
|||
|
Test range
(User defined test voltage)
|
1000 V, 2500 V, 5000 V,
10000 V, 15000 V
|
500 V, 1000 V, 2500 V,
5000 V, 10000 V
|
250 V, 500 V, 1000 V,
2500 V, 5000 V
|
|
|
Lock test voltage
|
40 V to 1 kV in 10 V steps;
1 kV to 15 kV in 25 V steps
|
40 V to 1 kV in 10 V steps,
1 kV to 5 kV in 25 V steps,
5 kV to 12 kV in 25 V steps
|
40 V to 1 kV in 10 V steps,
1 kV to 5 kV in 25 V steps,
5 kV to 12 kV in 25 V steps
|
|
|
Resistance range
|
10 kΩ to 35 TΩ
|
10 kΩ to 35 TΩ
|
10 kΩ to 15 TΩ
|
|
|
Accuracy
|
250 V
|
/
|
/
|
10 kΩ~50 GΩ, ±5%;
50 GΩ~500 GΩ, ±20%
|
|
500 V
|
/
|
10 kΩ~100 GΩ, ±5%;
100 GΩ~1 TΩ, ±20%
|
10 kΩ~100 GΩ, ±5%;
100 GΩ~1 TΩ, ±20%
|
|
|
1000 V
|
10 kΩ~200 GΩ, ±5%
200 GΩ~2 TΩ, ±20%
|
10 kΩ~200 GΩ, ±5%;
200 GΩ~2 TΩ, ±20%
|
10 kΩ~200 GΩ, ±5%;
200 GΩ~2 TΩ, ±20%
|
|
|
2500 V
|
10 kΩ~500 GΩ, ±5%
500 GΩ~5 TΩ, ±20%
|
10 kΩ~500 GΩ, ±5%;
500 GΩ~5 TΩ, ±20%
|
10 kΩ~500 GΩ, ±5%;
500 GΩ~5 TΩ, ±20%
|
|
|
5000 V
|
10 kΩ~1 TΩ, ±5%
1 TΩ~10 TΩ, ±20%
|
10 kΩ~1 TΩ, ±5%;
1 TΩ~10 TΩ, ±20%
|
10 kΩ~1 TΩ, ±5%;
1 TΩ~10 TΩ, ±20%
|
|
|
10000 V
|
10 kΩ~2 TΩ, ±5%
100 GΩ~20 TΩ, ±20%
|
10 kΩ~2 TΩ, ±5%;
2 TΩ~20 TΩ, ±20%
|
/
|
|
|
12000 V
|
/
|
10 kΩ~2 TΩ, ±5%;
2 TΩ~24 TΩ, ±20%
|
/
|
|
|
15000 V
|
10 kΩ~3 TΩ, ±5%
3 TΩ~30 TΩ, ±20%
|
/
|
/
|
|
|
Resistance resolution
|
0.01kΩ
|
|
Test modes
|
IR, IR (t), DAR, PI, SV, DD, ramp test,
voltage measurement
|
|
Short circuit current
|
1 mA, 2 mA, 3 mA, 4 mA, 5 mA, 6 mA
|
|
Insulation test alarm
|
100 kΩ to 999 GΩ
|
|
Voltage measurement
|
AC/DC: 5~660 V (45~65 Hz),
±3% rdg ±3 V, 0.1 Hz
|
|
Current measurement
|
0.01 nA~7.00 mA, ±5% rdg ±0.2 nA
|
|
Capacitance
|
10.0 nF~50.0 μF, ±10% rdg ±5 nF
|
|
Discharge rate
|
From 12 kV to 50 V, ≤0.47 s/uF
From 5 kV to 50 V, ≤0.25 s/uF
|
|
Temperature measurement
|
-20°C to 100 ℃, ±2 ℃
|
|
Filtering method
|
Hardware filtering, software filtering
|
|
Software filter settings
|
10 s, 20 s, 30 s, 60 s & adaptive
|
|
Timer range
|
Up to 99 minutes 59 seconds,
1 second minimum setting
|
|
Real-time output
|
Voltage, current, resistance
|
|
Display
|
7'', 800×480 industrial LED color display
|
|
Memory capacity
|
100 hrs logging @ 1 sec intervals
|
|
Data export
|
Export results and process data via USB
|
|
Communication interface
|
USB, bluetooth
|
|
Power supply
|
80~264 VAC, 47-63 Hz
|
|
Battery capacity
|
6200 mAh, 14.4 V
|
|
Battery life [(typical) continuous testing] with a 100 MΩ load
|
6 hrsat 10 kV (D1115+D1110)
7 hrs at 5 kV (D1105)
|
|
Battery charge time
|
3 hrs normal charging (220 V/50 Hz)
|
|
Operating temperature
|
-20°C to 50 °C
|
|
Storage temperature
|
-25°C to 65 °C
|
|
Humidity
|
<95% RH, non-condensing
|
|
Ip rating
|
IP65 (lid closed), IP40 (lid open)
|
|
Safety
|
CATIV 600 V to 3000 m
|
|
Net size
|
318×280×150 mm
|
|
Net weight
|
4.3 kg
|
Application
-
Commissioning and maintenance of distributed and generator power substation cables
-
Switch gear
-
Arresters
-
Motors and generators
-
Transformers