Overview
With a split and rugged design, we made T8 to be one of the world's most portable and powerful cable fault locators. We built in kinds of time-domain reflectometer(TDR) methods to pre-locate faults, like LV(low-voltage) TDR , Arc Reflection Method(ARM, optional), Impulse Current Decoupling method(ICE).For multiple types of cable faults.
All parts can be used independently. You can only use our TDR part to test the length of a cable, or can only use Pinpointer to locate a fault while you already have a surge generator.
- Fault location surge generator, model LP15/8
- Cable fault pre-locator (TDR), model WL20
- Cable fault pin-pointer, model PP20
Parameters
Fault location power LP15/8
|
|
DC voltage output
|
0-15 kV continuously adjustable
|
Output power
|
Peak 2000W
|
Capacitance
|
8μf
|
Max discharge energy
|
900J
|
Power supply
|
Lithium battery
|
Size
|
500×305×457 mm
|
Weight
|
29.5kg
|
Cable fault pre-locator TDR WL20
|
|
Low voltage impulse launching voltage
|
30V
|
Sampling frequency
|
200MHz
|
Max ranging scope
|
100km
|
Dead zone
|
2m
|
Max resolution
|
0.4m
|
Power supply
|
AC220V, 50Hz
|
Size
|
274×218×81 mm
|
Weight
|
3.5kg
|
Cable fault pin-pointer PP20
|
|
Precision of point positioning
|
0.1m
|
Precision of path location
|
0.1m
|
Precision of step voltage method
|
0.1m
|
Work mode |
Anti-noise mode
Strong noise reduction mode Background suppression noise reduction mode Point location mode: Intelligent Acousto-Magnetic Time Difference Mode |
Display mode
|
Color LCD
|
Power
|
Li-battery, 12h standby
|
Features
3.High safety: HV starts from 0,“emergency" button.
1.lV impulse method: applicable to locate low resistance fault, open circuit fault, total lengthand intermediate joint
2.Powerful noise reduction technology can effectively fiter out environmental interference, leaving only the "Crackling'discharge sound at the fault point in your ears.