Products

Insulating Conductor Covers for Live Line Work

Rigid Conductor Covers for Medium & High Voltage Applications

AHIS-CDT-3-15L & AHIS-CDT-2-30 & AHIS-CDT-3-15P & AHIS-CDT-3-HD

1.High-performance electrical insulation, withstanding up to 30 kV without breakdown or flashover
2.Advanced LDPE material offering excellent toughness, flexibility, and impact resistance
3.Strong resistance to chemicals, water, and environmental stress for long-term reliability
4.Integrated design with universal connection system for efficient and safe installation

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Product Overview

 Product Details

1.Model: AHIS-CDT-3-15L Conductor Cover

Features:

1.Material: LDPE (Low-Density Polyethylene).

2.Flexibility: Excellent elongation and toughness, resistant to bending, impact, and cracking.

3.Chemical Resistance: Strong resistance to most chemical reagents, including acids, alkalis, and salts, with minimal corrosion.

4.Water Resistance: Non-polar molecular structure prevents water absorption, making it suitable for humid environments.

5.Low-Temperature Resistance: Maintains flexibility even at -30 °C without becoming brittle.

6.Electrical Insulation Performance: Withstands 30 kV for 3 minutes without breakdown, overheating, or flashover. 

Model
AHIS-CDT-3-15L
Class
3
AC Proof Test Voltage
30 kV/3 min
AC Max Use Voltage
26.5 kV
Connector overlap length
15.5 cm
Inner diameter
4.5 cm
Length
155 cm
Weight
1.55 kg

2.Model: AHIS-CDT-2-30 Conductor Cover

Features:

1.This insulated protective cover is used during construction to approach live conductors and prevent accidental electric shocks.

Model
AHIS-CDT-2-30
Class
2
AC Proof Test Voltage
20 kV/3 min
AC Max Use Voltage
17 kV
Material
LDPE (Low-Density Polyethylene)
Inner diameter
35 mm
Length
3 m
Weight
1.2 kg

3.Model: Insulating Conductor Cover

Features:

1.Type: With universal adapter or without adapter for rubber glove application. 

2.Application: Insulates live conductors during live distribution network operations.

3.Installation: Use insulating gloves or a gun-style operating lever.

4.Production process: One-piece injection molding.

5.Features: Both the conductor shield and the insulator shield can be combined with similar products from leading brands, and the connection system offers universal compatibility.

6.Purpose: Protects workers from accidental contact with live components during line maintenance. 

Model
AHIS-CDT-3-15P
AHIS-CDT-3-HD
Class
3
AC Proof Test Voltage 
24 kV/1 min
AC Max Use Voltage
26.4 kV
Length
1.5 m
1.5 m
Inner diameter
50 mm
50 mm
Material
High-density polyethylene
High-density polyethylene
Weight
1.58 kg
2.16 kg