Insulating Conductor Covers for Live Line Work
Rigid Conductor Covers for Medium & High Voltage Applications
AHIS-CDT-3-15L & AHIS-CDT-2-30 & AHIS-CDT-3-15P & AHIS-CDT-3-HD
1.High-performance electrical insulation, withstanding up to 30 kV without breakdown or flashover
2.Advanced LDPE material offering excellent toughness, flexibility, and impact resistance
3.Strong resistance to chemicals, water, and environmental stress for long-term reliability
4.Integrated design with universal connection system for efficient and safe installation

Product Details
1.Model: AHIS-CDT-3-15L Conductor Cover
Features:
1.Material: LDPE (Low-Density Polyethylene).
2.Flexibility: Excellent elongation and toughness, resistant to bending, impact, and cracking.
3.Chemical Resistance: Strong resistance to most chemical reagents, including acids, alkalis, and salts, with minimal corrosion.
4.Water Resistance: Non-polar molecular structure prevents water absorption, making it suitable for humid environments.
5.Low-Temperature Resistance: Maintains flexibility even at -30 °C without becoming brittle.
6.Electrical Insulation Performance: Withstands 30 kV for 3 minutes without breakdown, overheating, or flashover.

| Model |
AHIS-CDT-3-15L
|
|
Class
|
3 |
|
AC Proof Test Voltage
|
30 kV/3 min
|
|
AC Max Use Voltage
|
26.5 kV
|
|
Connector overlap length
|
15.5 cm
|
|
Inner diameter
|
4.5 cm
|
|
Length
|
155 cm
|
|
Weight
|
1.55 kg
|
2.Model: AHIS-CDT-2-30 Conductor Cover
Features:
1.This insulated protective cover is used during construction to approach live conductors and prevent accidental electric shocks.

| Model |
AHIS-CDT-2-30
|
|
Class
|
2 |
|
AC Proof Test Voltage
|
20 kV/3 min
|
|
AC Max Use Voltage
|
17 kV
|
|
Material
|
LDPE (Low-Density Polyethylene)
|
|
Inner diameter
|
35 mm
|
|
Length
|
3 m
|
|
Weight
|
1.2 kg
|
3.Model: Insulating Conductor Cover
Features:
1.Type: With universal adapter or without adapter for rubber glove application.
2.Application: Insulates live conductors during live distribution network operations.
3.Installation: Use insulating gloves or a gun-style operating lever.
4.Production process: One-piece injection molding.
5.Features: Both the conductor shield and the insulator shield can be combined with similar products from leading brands, and the connection system offers universal compatibility.
6.Purpose: Protects workers from accidental contact with live components during line maintenance.


|
Model
|
AHIS-CDT-3-15P
|
AHIS-CDT-3-HD
|
|
Class
|
3
|
|
|
AC Proof Test Voltage
|
24 kV/1 min
|
|
|
AC Max Use Voltage
|
26.4 kV
|
|
|
Length
|
1.5 m
|
1.5 m
|
|
Inner diameter
|
50 mm
|
50 mm
|
|
Material
|
High-density polyethylene
|
High-density polyethylene
|
|
Weight
|
1.58 kg
|
2.16 kg
|