VLF-90KV Portable Hipot Test System
Overview
Parameters
TECHNICAL DATA | |
Output voltage | 90 kVpeak |
Frequency | 0.1Hz、0.05Hz、0.02Hz |
Load | 0.1Hz , 1.1µF max |
0.05Hz , 2.2µF max | |
0.02Hz,5.5µF max | |
Applicable cable voltage range | 6-35kV power cables |
Voltage waveform distortion | ≤5% |
Operating temperature | -10℃~+40℃ |
Storage temperature | -30°C-60°C |
Humidity | ≤85%RH |
Weight | controller-5.8KG & booster55KG |
Features
Unique advantages
Performance comparison of various withstand voltage test equipmen:
Easy to operate: simple wiring, fool operation
The instrument consists of two parts: controller and booster.Wiring instructions: connect the control output special line, high voltage output special line and grounding wire equipped with the product according to the method shown in figure.
The test process is fully automated
Self-inspection →boosting →constant amplitude output →Shutdown
Applications